The Stairwell Timer node manages a timed digital output.
When the Input connector receives the value 1, the node sends 1 to the Output connector and starts a timer.
When the configured time expires, the node sends 0 to the Output connector.
The node also provides retrigger, manual OFF, pre-warning, time override and remaining-time functions.
Behaviour of Stairwell Timer
| Connector | Type | Description |
|---|---|---|
| Input | Input | Starts the timer when it receives 1. Depending on the configuration, it can also stop the timer when it returns to 0. |
| ON time override | Input | Allows the configured ON duration to be overridden. |
| Output | Output | Timed digital output controlled by the node. |
| Warning | Output | Becomes 1 shortly before the timer expires, according to the configured warning time. |
| Time left | Output | Returns the remaining time before the timer expires. |
| Property | Description |
|---|---|
| Time for ON | Defines how long the Output remains equal to 1 after activation. |
| Retriggerable | When enabled, receiving another value 1 on Input restarts the timer. |
| Manual OFF | When enabled, the Output is immediately switched to 0 when Input returns to 0. |
| Warning before OFF | Defines how long before timer expiration the Warning output becomes 1. |
The Stairwell Timer is activated when:
Input = 1
At that moment:
When the timer expires:
Output = 0
If the node is configured with a warning period, the Warning output becomes active shortly before the timer expires.
The Time for ON property defines the normal activation time.
Conceptually:
Input = 1 → Output = 1 for Time for ON
When this time has elapsed:
Output = 0
For example:
| Property | Value |
|---|---|
| Time for ON | 120 seconds |
when the node is activated, the Output remains equal to 1 for 120 seconds.
When Retriggerable is enabled, the active timer can be restarted by receiving another activation command.
For example, assume:
Time for ON = 60 seconds
and the timer has 20 seconds remaining.
If the Input receives 1 again, the countdown restarts from the configured activation time.
Conceptually:
New Input = 1 → Timer restarts
Retriggerable mode is useful when every new activation request must extend the ON period.
When Retriggerable is disabled, a new activation command does not restart the timer while the current timing cycle is already active.
The Manual OFF property determines whether the Input can immediately switch the output OFF.
When Manual OFF is enabled:
When Manual OFF is disabled:
The Warning output provides an advance indication that the activation time is about to expire.
The warning interval is configured using:
Warning before OFF
When the remaining time reaches the configured warning interval, and Output is still equal to 1:
Warning = 1
This signal can be used to inform another logic function that the timed activation is close to ending.
The Warning output becomes active only shortly before the configured OFF event, while the main Output is still active.
Assume:
| Property | Value |
|---|---|
| Time for ON | 120 seconds |
| Warning before OFF | 10 seconds |
The sequence is:
The ON time override input allows the normal activation duration to be changed.
Instead of always using the value defined by Time for ON, the node can use an alternative duration supplied through this connector.
This is useful when the same Stairwell Timer must operate with different timing values according to the current system condition.
Suppose the normal configuration is:
Time for ON = 60 seconds
but another logic provides an override value corresponding to a longer activation period.
The node can then use the overridden duration instead of the standard configured value.
This allows the timing to be adjusted dynamically without changing the node configuration.
The Time left output provides the remaining timer duration.
During the active countdown, this value decreases as the timer approaches expiration.
This output can be used for:
Assume the following configuration:
| Property | Value |
|---|---|
| Time for ON | 60 seconds |
| Retriggerable | Enabled |
| Manual OFF | Disabled |
| Warning before OFF | 10 seconds |
When:
Input = 1
the node sets:
Output = 1
and starts a 60-second timer.
After 50 seconds:
Warning = 1
because only 10 seconds remain.
If another activation command is received before expiration and Retriggerable is enabled, the timer restarts.
If no new activation is received, after 60 seconds:
Output = 0
Assume:
Manual OFF = Enabled
and the timer is currently running.
If:
Input = 0
before the timer expires, the node immediately sets:
Output = 0
and stops the current timer.
Assume:
Time for ON = 90 seconds
The timer starts and 30 seconds remain.
If the Input receives 1 again and Retriggerable is enabled, the timer restarts from:
90 seconds
The output therefore remains active for a new complete timing period.
The Stairwell Timer is useful whenever a digital output must remain active for a limited period.
Typical applications include:
The Stairwell Timer can be tested using the Logic Module simulation tools.
A typical test procedure is the following: