Modbus

The Modbus protocol enables data exchange between automation devices over serial or Ethernet communication. Through the Gateway Modbus and Gateway Modbus Slave objects, the Thinknx server can read and write Modbus values, make them available to the supervision system, and exchange them with the KNX system.

This guide describes:

Fundamental concepts

Master and Slave

In Modbus communication, the Master initiates requests, while the Slave responds to the read or write operations it receives. A Slave does not initiate communication with the Master or with other Slaves.

When the Gateway Modbus object is used, the Thinknx server operates as a Master and polls one or more Slave devices. It can therefore read their data cyclically or send write commands.

When the Gateway Modbus Slave object is used, the Thinknx server exposes its Datapoints to an external Master, which can read or write them according to the configured settings.

In Modbus TCP implementations, the terms Client and Server are also used. From a communication perspective, the Client sends the request and the Server responds. In the terminology used by the Configurator, the Gateway Modbus Master normally acts as the Client, while the Slave device acts as the Server.

Modbus data areas

Modbus data is organised into four main areas.

Data area Size Standard access Read functions Write functions
Coil 1 bit Read and write 1 5 or 15
Discrete Input 1 bit Read only 2 —
Input Register 16 bits Read only 4 —
Holding Register 16 bits Read and write 3 6, 16 or 22

The data area is not determined only by the number shown in the device manual. The Modbus Function used determines whether the server must access, for example, a Coil or a Holding Register.

Modbus functions

The main functions available in the configuration are summarised in the following table.

Function Name Use
1 Read Coils Reads the status of one or more Coils.
2 Read Discrete Inputs Reads one or more digital inputs.
3 Read Holding Registers Reads one or more Holding Registers.
4 Read Input Registers Reads one or more Input Registers.
5 Write Single Coil Writes the status of a single Coil.
6 Write Single Holding Register Writes a single Holding Register.
15 Write Multiple Coils Writes multiple consecutive Coils.
16 Write Multiple Holding Registers Writes multiple consecutive Holding Registers.
22 Mask Write Register Modifies selected bits within a Holding Register.

The function must be supported by the device and must correspond to the data area specified in its Modbus documentation.

Modbus addressing and Thinknx offset

Device manuals do not always use the same addressing system. Some number registers starting from 1, while others show the protocol address directly, starting from 0.

The Thinknx server automatically applies an offset of -1 to the address entered in the Configurator.

Transmitted address = Address entered in the Configurator - 1
Address entered in the Configurator Address transmitted by the server
1 0
10 9
100 99

If the manual numbers registers starting from 1, the corresponding number can normally be entered directly in the Configurator. The server will then automatically apply the offset.

If the manual already shows the protocol address starting from 0, enter the value increased by 1 in the Configurator. For example, to transmit protocol address 0, address 1 must be configured.

The traditional notations 00001, 10001, 30001, and 40001 also identify the data area:

Traditional notation Data area First protocol address
00001 Coil 0
10001 Discrete Input 0
30001 Input Register 0
40001 Holding Register 0

For example, notation 40001 normally identifies the first Holding Register. In the Thinknx Datapoint, select the Function associated with Holding Registers and configure the numeric address required by the Configurator, without automatically entering the complete value 40001.

A typical configuration in this case is:

Information in the manual Data Address in the Configurator Transmitted address
Holding Register 40001 1 0

Warning: before configuring all Datapoints, always verify the convention used by the manufacturer by reading a single known value. Manually applying an additional -1 when the server already applies it results in the previous register being read.

Converting hexadecimal addresses

Some Modbus manuals show Datapoint addresses in hexadecimal format, normally identified by the 0x prefix. Before entering an address in the Configurator, convert it to the corresponding decimal value.

The conversion can be performed, for example, using the Windows Calculator in Programmer mode:

For example:

0x0010 = 16

Converting from hexadecimal to decimal does not change the Thinknx offset rule. If 0x0010 already represents the protocol address, its decimal value is 16 and 17 must be entered in the Configurator so that the server transmits address 16.

Information in the manual Decimal value Data Address in the Configurator Address transmitted by the server
0x0010 16 17 16 (0x0010)

Warning: hexadecimal notation only indicates the numeric base. It does not indicate whether the manufacturer uses zero-based or one-based numbering. Verify this information in the device manual or by performing a test read.

Required information

Before configuring the Gateway Modbus, obtain the device manual or Modbus table and identify:

Also verify that the required communication port and, when applicable to the server model, the relevant Modbus licence are available on the server.

It is advisable to verify this information using an external Modbus program before configuring the complete integration in Thinknx.

Gateway Modbus – Thinknx server as Master

Gateway modbus

The Gateway Modbus object allows the Thinknx server to operate as a Modbus Master. The server cyclically polls the configured devices and can write values through Datapoints, the KNX gateway, or object commands.

To add the gateway, open the System section of the project, right-click the main node, and add the Gateway Modbus object from the gateway category.

Communication types

The Communication Type property defines the method used by the server.

Modbus Serial

This mode is used to connect the server directly to a serial bus, normally via RS485.

All devices on the same serial bus must use compatible communication parameters and must have a unique Slave address.

Modbus Serial on TCP

This mode is used when the serial bus is reached through an Ethernet-to-serial converter. The converter transports serial communication over the network without converting it into native Modbus TCP communication.

The port must match the one configured in the converter. It does not necessarily have to be the standard port 502.

Modbus TCP

This mode is used to communicate directly with a Modbus TCP device.

Modbus Serial on TCP and Modbus TCP are not equivalent. Select the mode according to the protocol actually supported by the device or converter.

General parameters

A very short Poll Interval increases traffic and may cause timeouts or instability, especially on serial buses with many devices. Start with a small number of Datapoints and a conservative interval, then reduce it only after verifying communication stability.

Configuring Master Datapoints

Open the Datapoints collection, add a new item, and configure the required parameters.

Gateway modbus

Identification and address

Use descriptive names, such as Supply temperature, Pump alarm, or Zone 1 setpoint, so that Datapoints can be easily identified when selected by other objects.

Data type and functions

For example, an Input Register is normally read using Function 4 and cannot be written. A Holding Register is normally read using Function 3 and can be written using a function supported by the device, such as Function 6 or Function 16.

Value extraction and conversion

For example, if the device returns 235 to represent 23.5 °C, use a conversion factor of 0.1.

Before applying the conversion factor, verify that the raw value and its sign are interpreted correctly. An incorrect data type may produce apparently random values or values far outside the expected range.

Reuse

The Reuse property allows a completed read operation to be reused when multiple Datapoints extract different bits from the same address.

For example, if a Holding Register contains sixteen digital states, create multiple Datapoints with the same Slave Address and Data Address, changing only the Bit Number:

The driver reads the register only once and uses the received value to extract the different bits. This reduces the number of requests sent to the Slave and improves polling speed.

Force Rewrite

When Force Rewrite is enabled, the server cyclically rewrites the last value sent to the Datapoint. The frequency is defined by the general Write Refresh Interval property of the Gateway Modbus.

Use this function only when the device requires periodic command refreshing. Do not enable it indiscriminately, as it increases traffic and the number of write operations.

KNX Gateway

By enabling KNX Gateway, the Datapoint can exchange its value with the KNX bus.

The standard data flow is:

Modbus device → Gateway Modbus → KNX feedback group

Enabling bidirectional communication adds the opposite flow:

KNX command group → Gateway Modbus → Modbus device

Verify that the KNX Data Type is compatible with the Modbus value and any Conversion Factor applied.

Gateway Modbus commands

The object commands allow Modbus write operations to be triggered from scenes, logics, buttons, or other Thinknx objects.

Function 5 – Write Single Coil

Writes the status of a single Coil.

In the Configurator, the command is named Send Modbus value with function 5 and uses the following parameters:

The device must support Function 5 at the selected address.

Gateway modbus Gateway modbus

Function 6 – Write Single Holding Register

Writes a single Holding Register.

In the Configurator, the command is named Send Modbus value with function 6 and uses the following parameters:

At Modbus protocol level, Function 6 operates on a single 16-bit register. Although the parameter is named Coil Address in the Configurator, for this function it identifies the address of the Holding Register to be written. Check the device manual for the accepted value format and range.

Gateway modbus Gateway modbus

Function 15 – Write Multiple Coils

Function 15, also known as Write Multiple Coils, writes the status of multiple consecutive Modbus Coils simultaneously.

Warning: to trigger Function 15 from the supervision interface, use a Generic Command associated with the Send Modbus Word with function 15 command. Do not use a Light object, because Function 15 requires all the parameters needed to write multiple consecutive Coils and does not handle a simple ON/OFF command for a single Coil.

Each Coil represents one bit:

The Coils are written starting from the address specified in First Register Address. The software uses a single decimal value to define the Coil states and internally converts it to binary. The least significant bit corresponds to the first Coil, the next bit to the second Coil, and so on.

To set the first 10 Coils to ON:

1111111111 = 1023

To set the first 20 Coils to ON:

11111111111111111111 = 1048575

In general, to set the first N consecutive Coils to ON:

Value = 2ᴺ - 1
Number of Coils Decimal value
8 255
10 1023
16 65535
20 1048575

Individual Coils can also be controlled by setting only the corresponding bits. For example:

00000101 = 5

Value 5 sets the first and third Coils to ON, leaving all other Coils OFF.

Command parameters:

Gateway modbus

Function 16 – Write Multiple Holding Registers

Writes one or more consecutive Holding Registers.

In the Configurator, the command is named Send Modbus value with function 16 and uses the following parameters:

The configured size must be consistent with the number of registers and the value type required by the device.

Gateway modbus Gateway modbus

Function 22 – Mask Write Register

Function 22 modifies selected bits within a Holding Register without treating the register as a simple complete write command.

In the Configurator, the command is named Send Modbus Word with function 22 and uses the following parameters:

Initially verify the meaning of the mask and the expected result on a test register or using a Modbus simulator.

Gateway modbus

Master configuration examples

The following examples use demonstration values. Before applying them to a real device, replace all parameters with those specified in the relevant Modbus manual.

Example 1: reading a serial Holding Register

The objective is to read a temperature from a device with the following characteristics:

Gateway configuration:

Property Value
Communication Type Modbus Serial
Port Number Serial port used by the server
Baud Rate 9600
Data Length 8
Parity None
Stop Bits 1

Datapoint configuration:

Property Value
Name Device temperature
Slave Address 1
Data Address 10
Address transmitted by the server 0
Data Type Corresponding unsigned 16-bit type
Read Function Function 3
Conversion Factor 0.1

The expected value in Thinknx is 23.5.

Gateway modbus

Example 2: manual using zero-based protocol addresses

The manual explicitly specifies Protocol Address 25. Since this is already the address transmitted on the protocol, enter 26 in the Configurator.

Item Address
Address specified in the manual 25
Data Address in the Configurator 26
Address transmitted by the server 25

Gateway modbus

Example 3: reading multiple states from the same register

A Holding Register contains several alarm states, one for each bit.

Create multiple Datapoints with the same Slave Address, Data Address, Data Type, and Read Function values. Configure a different Bit Number for each alarm.

Disable Reuse on the first Datapoint. Enable Reuse on the subsequent Datapoints so that the server reads the register only once and reuses the received value.

Gateway modbus Gateway modbus

Example 4: Modbus–KNX integration

To send a temperature read from Modbus to the KNX bus:

  1. Configure and verify the Modbus Datapoint first.
  2. Enable KNX Gateway.
  3. Select the KNX Data Type corresponding to the temperature.
  4. Configure KNX Group from Modbus with the feedback group.
  5. Enable Send if Change if the value should be sent only when it changes.

To also allow writing from KNX to Modbus:

  1. Verify that the register is writable and that the Write Function is correct.
  2. Enable Enable KNX to Modbus.
  3. Configure Different KNX group with the command group.
  4. Send a test value and verify the response from the device.

Gateway modbus

Example 5: reading via Modbus TCP

The objective is to read Holding Register 10 from a Modbus TCP device with IP address 192.168.1.50, port 502, and Unit ID 1.

Gateway configuration:

Property Value
Communication Type Modbus TCP
IP Address 192.168.1.50
IP Port 502

Datapoint configuration:

Property Value
Slave Address 1
Data Address 10
Address transmitted by the server 9
Read Function Function 3

After uploading the project, verify that the server opens the TCP connection and receives a valid response from the device before adding other Datapoints.

Gateway modbus Gateway modbus

Gateway Modbus Slave

The Gateway Modbus Slave object allows the Thinknx server to expose Datapoints to an external Master. The Master can read or write the available values according to the configured functions and addresses.

Gateway modbus

Communication parameters

The Communication Type property defines the communication method.

For Modbus Serial, the following properties are available:

For Modbus Serial on TCP or Modbus TCP, the IP Port property defines the port on which Gateway Modbus Slave listens. A remote IP address is not required because the Thinknx server operates as a Slave and waits for the Master to connect.

Additional properties:

Slave Datapoint

The following properties are available for each Datapoint:

Usage example

To make a temperature available from the KNX bus to an external system:

  1. Add Gateway Modbus Slave.
  2. Configure the communication and the Device Address.
  3. Create a Datapoint with the required address, function, and data type.
  4. Associate the KNX Group containing the temperature value.
  5. Upload the project to the server.
  6. Use an external Modbus Master to read the configured address.
  7. Compare the received value with the value on the KNX bus.

Commissioning and verification

Initially, perform the verification using only one device and one Datapoint. After confirming that communication is working, add the remaining values.

Testing the device with Modbus Poll

Modbus Poll can be used as an external Master to test a Slave device independently of Thinknx.

Recommended procedure:

  1. Connect the PC to the device through the network or a serial adapter.
  2. Configure the parameters specified in the device manual.
  3. Set the Slave Address, Function, address, and register quantity.
  4. Read a single known value.
  5. Check both the address specified in the manual and whether it uses zero-based or one-based addressing.
  6. Record the working configuration and reproduce it in Gateway Modbus Thinknx.

If Modbus Poll cannot communicate with the device, resolve the issue before proceeding with the Thinknx configuration.

Testing the server with Modbus Slave

Modbus Slave can be used to simulate the device and observe the requests sent by the Thinknx server when it operates as a Master.

This test makes it possible to check:

For a Modbus TCP test, configure Gateway Modbus with the IP address of the PC running the simulator. Verify that the firewall and TCP port allow the connection.

Modbus Poll and Modbus Slave are available from the Modbus Tools website.

Analysing Modbus TCP with Wireshark

Wireshark can capture Modbus TCP traffic and analyse the requests and responses exchanged over the network.

Useful filters:

mbtcp
modbus
tcp.port == 502
ip.addr == 192.168.1.100

Replace the example IP address with the address of the device. The capture can be used to check the TCP connection, Function Code, addresses, requested quantities, data, and any error responses.

Wireshark cannot directly capture a Modbus RTU bus through a standard network interface. Serial traffic requires an interface and capture method suitable for the bus in use.

Troubleshooting

The device does not respond

Check:

Before modifying the Thinknx project, test the device with Modbus Poll or an equivalent tool.

The wrong register is read

The value is incorrect

Reading works but writing does not

Communication is unstable

The Modbus value is not sent to KNX

Modbus Exception

The most common exception responses are:

Code Meaning Main check
01 Illegal Function The function is not supported by the device.
02 Illegal Data Address The requested address or range is not available.
03 Illegal Data Value The requested value or quantity is not valid.
04 Server Device Failure The device could not complete the operation.

Always refer to the device manual, as the manufacturer may define additional conditions.

Quick diagnostic procedure

  1. Gather all parameters from the Modbus manual.
  2. Test the device with Modbus Poll or an equivalent tool.
  3. Read a single known value.
  4. Identify the addressing convention.
  5. Create only one Datapoint in Gateway Modbus Thinknx.
  6. Verify the transmitted address, taking the -1 offset into account.
  7. Check the raw value without conversions.
  8. Then verify the Data Type and Conversion Factor.
  9. Test writing, if required.
  10. Add the KNX gateway only after verifying Modbus communication.
  11. Gradually extend the configuration to the other Datapoints.